Daikin Applied has introduced Reference Architecture D60-W Water-Cooled Chillers with Dry Coolers, a 60 MW cooling reference design for “AI factories” built around the NVIDIA DSX AI Factory Platform with NVIDIA Vera Rubin NVL72. The company describes D60-W as a rack-to-ambient blueprint that ties together rack cooling, central plant equipment, heat rejection, and controls in a single system.
D60-W is designed to support a 60 MW IT load across six deployable units. In the reference design, liquid cooling handles 92% of the load, with air cooling covering the remaining 8%. The architecture uses two temperature loops: a high-temperature liquid loop serving coolant distribution units (CDUs), and a dedicated low-temperature loop serving air-cooling rack containment units, which Daikin Applied says is intended to improve overall plant efficiency.
The central plant is built around Daikin Applied’s oil-free Magnitude WME magnetic bearing centrifugal chillers, with capacities up to 10 MW. In suitable climates, dry coolers are intended to carry most of the annual cooling load, with chillers supporting operation during the hottest days. Daikin Applied points to oil-free technology as a way to avoid oil heaters, pumps, oil management, and periodic run cycles associated with traditional oil-lubricated chillers, reducing standby energy use and maintenance. It also says eliminating oil-related startup delays helps the cooling plant recover faster after standby, protecting GPU availability.
On the rack side, D60-W is primarily liquid-cooled through CDUs, with DDC Solutions S-Series rack containment units (RCUs) capturing remaining heat at the rack and moving it to the low-temperature loop. Daikin Applied says each rack includes fire suppression and water-loop protection, and that operators can run air-cooled, liquid-cooled, or hybrid configurations side by side.
For resiliency, Daikin Applied includes its RideThrough and RapidRestore chiller technologies to address brief power disturbances and restarts after shutdown. The reference design also calls for redundancy across the cooling system—from rack infrastructure through the dry coolers—to maintain uptime during equipment outages and planned maintenance.
D60-W also avoids evaporative cooling towers in favor of dry coolers, which eliminates cooling-tower make-up water and is intended to support low water usage effectiveness (WUE). Operationally, the design switches between dry cooling, hybrid cooling, and full mechanical cooling based on outdoor conditions: in dry cooling mode the chiller compressors are off, and in hybrid mode waterside economizers precool return water before chillers pick up the remaining load.
System coordination is handled by Daikin Applied’s iDCM supervisory layer, which manages load sharing, balances equipment operating hours, and controls transitions between operating modes, with integration into site management systems for centralized visibility. “A cooling decision at the rack carries implications for water temperatures, flow requirements, plant operation and heat rejection,” said Karim Shalash, director of Data Center Solutions at Daikin Applied.
Daikin Applied said its CDU and data center dry cooler are under development, with availability targeted for the second half of 2027. More details are available on the Reference Architecture D60-W page.
Source: Daikin Applied